Key Findings
The PU100 large-scale fire test demonstrated that fire propagation was effectively controlled, with no thermal runaway occurring in adjacent modules. Despite 50 percent of the cells in the initiating module being heated simultaneously, adjacent modules maintained normal post-test voltage readings of 53.2 V. Furthermore, the system exhibited post-fire stability, self-extinguishing after 43 minutes with no observed re-ignition over the following 24 hours.
Technical Details
The testing provided measurable evidence regarding thermal exposure and deployment density:
- Thermal Margins: Wall temperature rise remained below 80°C (against a 97°C limit), and ceiling steel-beam temperature stayed below 250°C (against a 538°C limit), representing margins of more than 17°C and 288°C, respectively.
- Compact Deployment: The test utilized 10 cabinets at 100 percent state of charge. The configuration included zero side-by-side clearance, 20 mm back-to-back spacing, and 850 mm face-to-face spacing. No fire spread to adjacent or target cabinets was observed.
- Debris Control: No flaming debris escaped the cabinet, exceeding the assessed criterion of no flaming debris beyond 1.5 m.
Background and Context
Presented at RE+ 2026, these results are intended to assist data center operators in making informed decisions regarding system selection, installation design, and recovery planning. Ampace, established in 2021, provides lithium-ion batteries for various applications, including energy storage, robotics, and e-mobility. According to company records, Ampace has recorded zero safety incidents across its supplied battery packs and cells.
Significance and Outlook
By converting safety questions into measurable evidence—specifically regarding where propagation stops and how much heat reaches surrounding structures—the PU100 results support project-specific engineering assessments for AI data centers. These findings provide a framework for assessing fault isolation and the potential impact of battery failures on surrounding equipment in high-density installations.
Source: https://finance.yahoo.com/energy/articles/ampace-presents-pu100-fire-test-061100717.html
Get our weekly technology intelligence — free
Receive an infographic that lets you judge at a glance whether each field’s analysis report is worth reading.
Subscribe Free — Weekly Tech Intelligence
By subscribing, you’ll receive Troy-Technical’s weekly technology intelligence newsletter.
- Your email and selected fields are used only to deliver the newsletter.
- We never share your information with third parties.
- You can unsubscribe anytime via the link in each email.
See our Privacy Policy for details.
Takes about a minute · Unsubscribe anytime